Troubleshooting
Most service questions can be solved over the phone by a question and answer dialog. Below are standard troubleshooting quidelines that may answer your question immediately. Also check our Frequently Asked Questions and Installation and Maintenance Instructions for other possible solutions. Or call our Technical Support Group at 617-926-1000 or fax your request to 617-926-4354.

If you are unable to find your solution in our troubleshooting guide, please send an e-mail outlining your problem to Ask The Expert. It will be sent to a UE Technical Representative who will contact you direct (make sure to include your phone and fax numbers). In the unlikely event the problem remains unresolved, instructions on returning the product to our factory Field Service group will be given over the phone.

Electromechanical Pressure and Vacuum Switches
Electromechanical Temperature Switches

 

Electromechanical Pressure and Vacuum Switches
Problem: Switch won't actuate
Possible Causes Solution
Electrical:
  1. Is it wired correctly?
  2. Too much current-burned out switch?
  3. Dry circuit-too little current?
  4. Is a wire grounded?
  5. Is control head subjected to high temperature?
Mechanical:
  1. Has set point changed?
  2. Plunger binds
  3. Malfunctioning pressure sensor
    1. Is plunger moving or is it depressed regardless of pressure exerted.
    2. Has control been over- pressurized so movement is distorted?
    3. Has sensor been subjected to corrosive media?
  4. Pivots binding
Electrical:
  1. Re-wire
  2. Substitute higher contact switch
  3. Substitute gold contact switch to minimize oxidation
  4. Re-wire
  5. Use hi-ambient switch

Mechanical:

  1. Re-set
  2. Replace plunger
  3. Replace sensor
    1. Replace sensor
    2. Replace sensor and protect from over-pressure
    3. Use sensor that resists medium or use chemical seal
  4. Check control ambient & overpressures

Problem: Sensor is not operating-or is leaking medium fluid
Possible Causes Solution
  1. Over pressured beyond control specifications
  2. Is medium corrosive?

  1. Replace sensor


Problem: Switch is chattering
Possible Causes Solution
  1. Vibration present?
  2. Pulses in pressure line?

  1. Mount away from vibration or order 12 Series unit.
  2. Use pulsation dampener in line

Back to Top

 

Electromechanical Temperature Switches
Problem: Switch won't actuate
Possible Causes Solution
Electrical:
  1. Is it wired correctly?
  2. Too much current-burned out switch?
  3. Dry circuit-too little current?
  4. Is a wire grounded?
  5. Is control head subjected to high temperature?
Mechanical:
  1. Has set point changed?
  2. Plunger binds
  3. Malfunctioning thermal assembly?
    1. Is plunder moving or is it depressed regardless of temperature at sensor.
    2. Does head of thermal assembly smell of chemicals or show liquid?
    3. Has control been over-temperatured so movement is distorted?
    4. Has capillary been crimped or cut?
    5. Has capillary or bulb or control head been attacked by corrosive medium or atmosphere?
  4. Pivots binding
Electrical:
  1. Re-wire
  2. Substitute higher contact switch
  3. Substitute gold contact switch to minimize oxidation
  4. Re-wire
  5. Use hi-ambient switch

Mechanical:

  1. Re-set
  2. Replace plunger
  3. Replace thermal assembly
  4. Check control ambient & overpressures

Problem: Sensor is not operating-or is leaking medium fluid
Possible Causes Solution
  1. Over temperature beyond control specifications
  2. Is medium corrosive?

  1. Replace sensor


Problem: Switch is chattering
Possible Causes Solution
  1. Vibration present?

  1. Mount away from vibration.

Back to Top